Зображення носить ознайомчий зміст
|
SIMATIC S7-300, Блок живлення PS 307 ВХІД: ~ 120/230В, ВИХІД: =24В/5A, Siemens Код:
6ES7307-1EA01-0AA0
Прайсова ціна (за курсом НБУ) (indicative)
Виробник
:
Наявність на європейському складі (доставка 1 тиждень):
21 days
|
Вага:
0.63 kg/шт
|
об'єм:
0.0016 m3/шт
|
|
|
|
|
Simatic S7-300, stabilized power supply PS307, 120-230VAC/ 24VDC 5A, Siemens
POWER SUPPLY PS307 24 V/5 A SIMATIC S7-300 STABILIZED POWER SUPPLY PS307 INPUT: 120/230 V AC OUTPUT: DC 24 V DC/5 A
|
|
|
Input:
|
Input 1-phase: |
AC |
Supply voltage
1 at AC Rated value
2 at AC Rated value
Note: |
120 V
230 V
Automatic range selection |
Input voltage
1 at AC
2 at AC : |
85 ... 132 V
170 ... 264 V |
Wide-range input: |
No |
Overvoltage resistance: |
2.3 × Vin rated, 1.3 ms |
Mains buffering at Iout rated, min.: |
20 ms; at Vin = 93/187 V |
Rated line frequency: |
50 ... 60 Hz |
Rated line range: |
47 ... 63 Hz |
Input current
at rated input voltage 120 V
at rated input voltage 230 V: |
2.3 A
1.2 A |
Switch-on current limiting (+25 °C), max.: |
20 A |
Duration of inrush current limiting at 25 °C maximum: |
3 ms |
I2t, max. 1.2: |
A2·s |
Built-in incoming fuse: |
T 3,15 A/250 V (not accessible) |
Protection in the mains power input (IEC 898): |
Recommended miniature circuit breaker: from 6 A characteristic C |
Output:
|
Output: |
Controlled, isolated DC voltage |
Rated voltage Vout DC: |
24 V |
Total tolerance, static: |
± 3 % |
Static mains compensation, approx.: |
0.1 % |
Static load balancing, approx.: |
0.5 % |
Residual ripple peak-peak, max.: |
50 mV |
Residual ripple peak-peak, typ.: |
10 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz): |
150 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz): |
20 mV |
Product function Output voltage adjustable: |
No |
Output voltage setting: |
- |
Status display: |
Green LED for 24 V OK |
On/off behavior: |
No overshoot of Vout (soft start) |
Startup delay, max.: |
2 s |
Voltage rise, typ.: |
10 ms |
Rated current value Iout rated: |
5 A |
Current range: |
0 ... 5 A |
Supplied active power typical: |
120 W |
Short-term overload current
on short-circuiting during the start-up typical
at short-circuit during operation typical: |
20 A
20 A |
Duration of overloading capability for excess current
on short-circuiting during the start-up
at short-circuit during operation: |
100 ms
100 ms |
Parallel switching for enhanced performance: |
Yes |
See more information from Downloadable Files.
|
|
|
File description
|
File type
|
Download link
|
|
|
|
Data Sheet
|
PDF
|
Download link
|
|
|
|
|
|